Homeowner Sample Exam Question #3
|
Correct answer is D:
Calculated Load [see 220.40] General Lighting Load: 3120 sq ft at 3 VA per sq ft = 9360 VA Minimum Number of Branch Circuits Required [see 210.11(A)] General Lighting Load: 9360 VA ÷ 120 V = 78 A Required circuits: 78 A ÷ 15 A = 5.2 This requires six 15-A, 2-wire circuits.