Homeowner Sample Exam Question #1
|
Correct answer is C:
Calculated Load [see 220.40] General Lighting Load: 1500 sq ft at 3 VA per sq ft = 4500 VA Minimum Number of Branch Circuits Required [see 210.11(A)] General Lighting Load: 4500 VA ÷ 120 V = 37.5 A This requires three 15-A, 2-wire or two 20-A, 2-wire circuits. Small Appliance Load: Two 2-wire, 20-A circuits [see210.11(C)(1)] Laundry Load: One 2-wire, 20-A circuit [see210.11(C)(2)] Bathroom Branch Circuit: One 2-wire, 20-A circuit (no additional load calculation is required for this circuit) [see210.11(C)(3)] Minimum Size Feeder Required [see 220.40]
General Lighting 4,500 VA Small Appliance 3,000 VA Laundry 1,500 VA Total 9,000 VA 3000 VA at 100% 3,000 VA 9000 VA – 3000 VA = 6000 VA at 35% 2,100 VA Net Load 5,100 VA Range (see Table 220.19) 8,000 VA Dryer Load (see Table 220.54 ) 5,500 VA Net Calculated Load 18,600 VA